Free Shipping on $50+   |   (877) 534-4621    | info@lightfixtureindustries.com

Exit Sign | Connecticut Approved Green | White Housing [EXCT-G]

This White Coated Aluminum ISA Exit Sign is designed to comply with the State of Connecticut Building Code requirements. This exit sign has 6" Green EXIT Lettering and a 6" International Symbol of Accessibility. This unit allows for ceiling, end and surface mounting.

93.00 93.0 USD 93.00

93.00

  • Operation Type

This combination does not exist.


Download Spec-Sheet:

UL Listed

This item has been tested and meets safety standards imposed by the Underwriters Laboratories (UL).

LED Lighting

This unit uses energy efficient and long lasting LED's.

Battery Included

This unit contains a battery for backup power. The battery must be connected during installation.

FEATURES

  • UL 924 Damp Location and State of Connecticut Build Code Approved
  • NiCad 3.6V 300mAh battery backup option
  • Universal 120/277 VAC operation
  • Universal mounting canopy included
  • Universal mounting pattern for surface mounting to a j-box
  • Low Energy consumption (Less than 5W)
  • Extruded aluminum housing with white finish
  • Selectable chevron directional arrows
  • Push-to-test switch
  • Charge rate / power on LED indicator light


SPECIFICATIONS

Dimensions
Width 2"
Height 7.625"
Length 18.625"
Weight 8.00 lb

WHAT'S INCLUDED

Green LED Connecticut Exit Sign

Two "EXIT" with ISA Faceplates

One Blank Faceplate

Mounting Canopy, Installation Instructions & Hardware

NiCad Battery - Must connect the battery after installation


CONSTRUCTION

The EXCT-G Exit Sign offers durable extruded aluminum housing with a white powder coat finish.

ILLUMINATION

The EXCT-G Exit Sign uniform illumination is achieved by use long-lasting, efficient ultra bright red or green LEDs.

EMERGENCY OPERATION

Upon failure of the normal utility power, an internal solidstate transfer switch automatically provides uninterrupted emergency operation for at least 90 minutes. The fully automatic solid-state, two-rate charger initiates battery charging to recharge a discharged battery in 24 hours.

BATTERY - BATTERY BACKUP

The EXCT-G Exit Sign is designed with a maintenance-free 3.6V 300mAh NiCad battery that provides a minimum emergency duration of 90 minutes. Recharge time of the battery is 24 hours.

OPERATIONAL TEMPERATURE

Temperature Ratings
Standard Option-10°C to 45°C / 14°F to 113°F


ELECTRICAL COMPONENTS

Dual voltage input 120/277 VAC operation. LED display indicates AC/ON. An external push button test switch allows maintenance personnel to quickly determine the operational status of the unit. Unit offers surge protected, solid state circuitry. Operation Temperature range -10°C to 45°C / 14°F to 113°F

INSTALLATION

The EXCT-G Exit Sign is suitable for surface wall, side and top mounting via included canopy. Universal mounting pattern on back faceplate allows for easy surface mounting to a j-box. Field selectable Chevron Arrows are included.

Mounting Configurations Explained

DIMENSIONS